HomeProductsContactKnowledge BaseOrdering InfoDistributorsCompany Info

Selecting alarm stages:

The majority of the E2S range of alarm sounders (and some
multi-function beacons) have 2, 3 or 4 'alarm stages'. Below
is a brief explanation of how the different stages are activated.


AC units:

Stage 1
– Apply power only
Stage 2 – Apply power and close contacts at 'S2-Stage2'
Stage 3 – Apply power and close contacts at 'S3-Stage3'
Stage 4
– (Programmable units ONLY) Apply power and close both contacts

Important: Stages must be switched via the separate 'C' common terminal not the neutral supply.



DC units:

Stage 1 – Apply power only
Stage 2 – Apply power and close contacts at 'S2-Stage2'
Stage 3 – Apply power and close contacts at 'S3-Stage3'
Stage 4
– (Programmable units ONLY) Apply power and close both contacts