Sound level ouputs are up to 117dB(A) at 1 metre with a choice of 32 alarm tones and 3 remotely selectable stages. The BEx range features enclosures manufactured from corrosion proof, marine grade copper free LM6 aluminium which is phosphated and powder coated. The radial horn on the compact BExS110-R distributes the warning signal omni-directionally. The radial horn is manufactured from high impact, fire retardant ABS.
All models have two M20 cable entries, large termination areas containing in & out terminals (Ex de version only) and an ingress protection of IP66/67 (Ex d) and IP66 (Ex de).
Maximum output: | 117dB(A) @ 1 metre [108dB(A) @ 10ft/3m] | |
Nominal output: | 110dB(A) @ 1m +/- 3dB – Tone 2 [101dB(A) @ 10ft/3m] | |
No. of tones: | 32 (UKOOA / PFEER compliant) | |
No. of stages: | 3 |Volume control: |
Max. 110dB(A); Min. 72dB(A) – Tone 2 |
Effective range: | 100m/328ft @ 1KHz | |
Voltages DC: | 12vdc; 24vdc; 48vdc | |
Voltages AC: | 115vac; 230vac |
Stage switching:|Negative or positive|
|Ingress protection:|S110D : IP66/67 S110E : IP66|
|Enclosure matl:|Marine grade copper free LM6
Aluminium|
|Enclosure finish:|Chromate & powder coated finish – anti-corrosion.|
|Colour:|RAL3000 Red
(others available on request)|
|BExS110 flare:|High impact UL94 V0
& 5VA FR ABS (Red)|
|BExDS110 flare:|Anti-Static High impact ABS (Black)|
|Cable entries:|Dual M20 ISO (one stopping plug inc)|
|Terminals:|0.5 – 2.5mm² (20-14 AWG)|
|Enclosure volume:|<2 litres|
|Line monitoring:|Blocking diode included
EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor
or diode (DC versions) can be fitted|
|Weight:|DC: 3.00kg/6.6Ibs AC: 3.20kg/7.04Ibs|
Version: | Voltage: | Current: | |
---|---|---|---|
12V dc | +/-25% | 195mA | |
24V dc | +/-25% | 265mA | |
48V dc | +/-25% | 130mA | |
115V ac | 50/60Hz | +10/-10% | 110mA |
230V ac | 50/60Hz | +10/-10% | 56mA |
Part Code: | Classification: | |
---|---|---|
BExS110DR** | ATEX / IECEx: II 2G Ex d IIB T4 Ta. -50° to +70°C II 2G Ex d IIC T4 Ta. -50° to +55°C |
|
GOST-R: 1ExdIICT4 Ta. -50° to +55°C |
||
BExS110ER** | ATEX / IECEx: II 2G Ex de IIB T4 Ta. -50° to +70°C II 2G Ex de IIC T4 Ta. -50° to +55°C |
|
GOST-R: 2ExdeIICT4 Ta. -50° to +55°C |
||
BExDS110DR** | ATEX / IECEx: II 2G Ex d IIB T4 Ta. -50° to +70°C II 2G Ex d IIC T4 Ta. -50° to +55°C II 2D Ex tD A21 IP67 T115 based on a max. Ta. of 70°C |
|
GOST-R: 1ExdIICT4 Ta. -50° to +55°C T100°C DIP A21 Ta T4 |
||
BExDS110ER** | ATEX / IECEx: II 2G Ex de IIB T4 Ta. -50° to +70°C II 2G Ex de IIC T4 Ta. -50° to +55°C II 2D Ex tD A21 IP66 T115 based on a max. Ta. of 70°C | |
GOST-R: 2ExdeIICT4 Ta. -50° to +55°C DIP A21 Ta T4 |
** = Voltage reference: | ||
Options: | 12DC, 24DC, 48DC, 115AC, 230AC | |
Add ‘-P’ to part number for Programmable version |