The D2xB1XH2 features a high output UL1971 rated 70.29cd, 10 Joule Xenon strobe warning light / beacon. Globally approved, the robust Type 4/4X, IP66 enclosure ensures suitability for all haz loc fire alarm and general signalling applications.
Request a quote for this product
Voltage
Cable entries
Stopping plug material
Guard material
Product version
Product option
Enclosure colour
Lens colour
Part Number:
D2xB1XH2
Request Price or enquire about this product
Enquire about
Haz Loc UL1971 Xenon Strobe

Description

Multiple D2xB1XH2 units will auto-synchronize when powered from the same power source removing the need for any additional sync modules in the circuit. One device, globally certified: NEC/CEC CI D2 and CII D2; NEC CI Zone 2 and Zone 22; CEC Zone 2 & 22 and CII D2; ATEX, IECEx Zone 2 & 22. UL1638/UL1971 & CAN-ULC-S526 tested – suitable for public mode fire alarm, ADA compliant, hearing impaired applications.

Downloads

Datasheet Datasheet.pdf
Installation Manual D211-01-251-IS_Issue_2__D2xB1XH1_XH2_.pdf
IECEx certificate IECEx_ULD_14.0004X_007_D2x.pdf
ATEX certificate DEMKO_14_ATEX_4786493904X_Rev7_D2x.pdf
UL certificate of compliance UL_CoC_-_20171013-E245313_Vol.1_Sec.2_D2xB.pdf
CSFM Listing CSFM_Listing_2279-0500_D2xB1_2024.pdf
UKCA Certificate UL21UKEX2131X_Rev._1_D2x.pdf
ECAS Ex Approval ECAS_23-12-94531_E23-12-097313_NB0007_D2x.pdf
Declaration of Conformity DC-061_Issue_K_D2x.pdf
Declaration of Conformity UKCA DC-102_Issue_B_D2x_UKCA.pdf
2D drawing (PDF) D211-05-251_Issue_1.pdf
2D drawing (DWG) D211-05-251_Issue_1.DWG
3D drawing (STEP) D211-05-251-3D_Issue_A.STEP
Wiring Schematic D211-06-251_Issue_2.pdf
Nameplate Drawing D211-09-251_Issue_1.pdf
Pole Mount & Sun Shade Drawing D217-05-242_Issue_1__D2xB1_.pdf
Hi-res product image 1 (TIFF) 1-31-080_D2xB1XH2-RC.tif

Features

  • UL1971/UL1638 Public mode fire
  • CAN/ULC-S526 Fire approved
  • 70.29 eff. candela
  • Synchronised for over 2 hours per UL1971
  • Xenon tube mechanically secured against vibration & shock
  • Marine grade aluminum enclosure
  • Ingress protection Type 4/4X/3R/13, IP66
  • High impact resistant Borosilicate glass lens
  • Stainless steel external and internal fixings
  • Duplicate, pluggable cable terminations, supervisory diode
  • Conduit mounting via integral 3/4" NPT entry
  • Surface mounting via user installed lugs
  • Pendant mounting via 3/4"NPT conduit entry
  • Dual 1/2"NPT and M20 cable entries
  • Supplied with haz loc rated stopping plugs/adaptors

Specification

Energy: 10 Joules (10Ws)
Source: Xenon strobe
Modes: 1Hz flash (60 fpm)
Effective cd: 70.29 cd – UL1971
Peak Candela: 1,000,000 cd – calculated from energy (J)
Effective cd: 500 cd – calculated from energy (J)
Synchronisation: Flash rates synchronise for a minimum of 2 hours per UL1971
Voltages: 24Vdc – 20-28Vdc
Ingress protection: IP rating per EN60529:IP66
Type rating per UL50E/NEMA250:4/4X/3R/13
Enclosure material: Marine grade LM6 aluminum alloy
Enclosure colour: Red
Lens colour: Clear
Lens material: Borosilicate glass dome
Cable entries: 2 x M20x1.5, 2 × 1/2"NPT, 1 × 3/4"NPT
Stopping plugs: Nickel Plated Brass plugs included – brass or stainless steel optional
Mounting: Conduit mount via 3/4" NPT entry
Surface mount via optional lugs
Ground/Earth stud: M5
Terminals: 0.5 – 2.5mm² (20-14 AWG)
Line monitoring: Blocking diode included
EOL can be factory fitted
Operating temp: -40 to +50°C [-40° to +122°F]
Storage temp: -40 to +70°C [-40° to +158°F]
Relative humidity: 95%
Weight: 1.5kg/3.31Ibs

Current Consumption

Nominal Voltage: In rush: Voltage range: Flash Rate setting: Nominal operating current:
24V dc 828mA <4.4ms 20-28V dc 1Hz flash (60 fpm) 609mA

Part Codes

Part Code: Identifier: Description:
Product type: D2xB1XH2 70.29cd 10 Joule Xenon Strobe warning light / beacon
Voltage: DC024 24V dc (20-28Vdc)
Cable entries: [e] M 2 × 1/2” NPT
2 x M20x1.5
1 × 3/4” NPT
Stopping plug material: [m] N
S
Nickel plated brass
Stainless Steel
Guard material & tag: [s] 0
3
5
No lens Guard
No lens guard with Equip. Tag
No lens guard with Equip. Tag & Duty Label
Product version: [v] H UL, cUL, ULC, IECEx, ATEX, CSFM
Product option:
[o]
1
T
X
Standard product
Tropicalisation
Custom configuration – contact E2S
Enclosure colour: [x] R Red
Lens colour: [y] C Clear
Accessories:
SP65-0001-A4
SP65-0003-A4
Pole Mount Bracket Kit St/St A4 (316)
Sunshade – St/St A4 (316)

Approvals

  • UL/cUL File ref: E245313
  • IECEx certficate: IECEx ULD 14.0004X
  • ATEX certificate: DEMKO 14 ATEX 4786493904X
  • CSFM certificate: 7300-2279:0500

Coding

  • NEC / CEC:
    Class I Div 2 ABCD T1 Ta -40°C to +50°C
    Class I Div 2 ABCD T2 Ta -40°C to +45°C
    Class II Div 2 FG T4A Ta -40°C to +50°C
    Class II Div 2 FG T5 Ta -40°C to +45°C
    Class III Div 1&2 Ta -40°C to +50°C
  • NEC:
    Class I Zone 2 AEx ec IIC T1 Gc Ta -40°C to +50°C
    Zone 22 AEx tc IIIC T105°C Dc Ta -40°C to +50°C
  • CEC:
    Class I Zone 2 Ex ec IIC T1 Gc X Ta -40°C to +50°C
    Zone 22 Ex tc IIIC T105°C Dc Ta -40°C to +50°C
  • IECEx & ATEX:
    II 3G Ex ec IIC T1 Gc Ta -40°C to +50°C
    II 3D Ex tc IIIC T105°C Dc Ta -40°C to +50°C
    See product manual for full voltage specific coding.