Enclosure: | Marine grade LM6 aluminium | ||||
Enclosure colour: | Red or Grey | ||||
Enclosure finish: | Chromate & powder coated finish | ||||
Ingress protection: | IP66/67 EN50029, Type 4/4X UL50E | ||||
Cable entries: | 2 × 3/4"NPT with 2 x M20x1.5mm or 2 × 1/2"NPT Stopping plug(s) included |
||||
Cable spec: | Solid core: 0.5-2.5mm2 AWG20-12 Stranded core: 0.5-2.5mm2 AWG24-14 |
||||
Terminals: | DIN Rail AKZ 2.5 × 6 | ||||
Max Input | 32Vdc: 1A, 24Vdc: 2A, 32Vac 50/60Hz: 5A – version E | ||||
Max Power | 1.25W – version E | ||||
Safety parameters: | Ui=30V, Ii=500mA, Pi=1100mW, Ci=0, Li=0 – version I & R | ||||
Stopping plugs: | Brass, Nickel Plated or Stainless Steel | ||||
Grounding stud: | M5 | ||||
Installation temp: | -40° to +50°C (-40°F to +122°F) | ||||
Storage temp: | -40° to +50°C (-40°F to +122°F) | ||||
Weight: | 1.5kg/3.31Ibs | ||||
Temperature and spacing data |
|||||
°F Setting |
°F Tolerance |
°C Setting |
°C Tolerance |
Spacing UL (ft) |
Spacing ULC (ft) |
140 | +7/-8 | 60 | +4/-5 | 50 | 50 |
160 | +7/-8 | 71 | +4/-5 | 25 | 25 |
190 | +7/-8 | 88 | +4/-5 | 50 | 50 |
210 | +7/-8 | 99 | +4/-5 | 25 | 50 |
225 | +7/-8 | 107 | +4/-5 | 25 | 50 |
275 | ±10 | 135 | ±6 | 25 | 50 |
325 | ±10 | 163 | ±6 | 50 | 50 |
360 | ±10 | 182 | ±8 | 25 | 50 |
450 | ±15 | 232 | ±10 | 25 | 50 |
500 | ±15 | 260 | ±10 | 50 | 50 |
600 | ±20 | 316 | ±12 | N/A | 50 |
725 | ±20 | 385 | ±12 | N/A | 50 |
Derating Factor for Ceiling Height – based on NFPA guidelines |
|||||
Ceiling Height Above | Up to and Including | Derating Factor | |||
m | ft | m | ft | - | |
0 | 0 | 3.05 | 10 | 1.00 | |
3.05 | 10 | 3.66 | 12 | 0.91 | |
3.66 | 12 | 4.27 | 14 | 0.84 | |
4.27 | 14 | 4.88 | 16 | 0.77 | |
4.88 | 16 | 5.49 | 18 | 0.71 | |
5.49 | 18 | 6.10 | 20 | 0.64 | |
6.10 | 20 | 6.71 | 22 | 0.58 | |
6.71 | 22 | 7.32 | 24 | 0.52 | |
7.32 | 24 | 7.93 | 26 | 0.46 | |
7.93 | 26 | 8.54 | 28 | 0.40 | |
8.54 | 28 | 9.14 | 30 | 0.34 |
Part Code: | Identifier: | Description: |
---|---|---|
Product type: | D2xH1 | Heat Detector |
Element orientation: [d] | H V |
Horizontal Vertical |
Element guard:[g] | N G |
No guard With guard |
Temperature code:[t] | 01 02 03 04 05 06 07 08 09 10 11 12 |
140°F / 60°C 160°F / 71°C 190°F / 88°C 210°F / 99°C 225°F / 107°C 275°F / 135°C 325°F / 163°C 360°F / 182°C 450°F / 232°C 500°F / 260°C 600°F / 316°C 725°F / 385°C |
Cable entries:[e] | A B C Note: |
2 x M20 & 2 × 1/2"NPT (Vertical orientation) 2 x M20 (Horizontal orientation) 2 × 1/2"NPT (Horizontal orientation) All types also contain 2 × 3/4” NPT side & 1 × 3/4” NPT pendant entries |
Stopping plug/adaptor material: [m] | B N S |
Brass Nickel Plated Stainless Steel |
Equipment tag: [s] | 1 2 3 6 7 |
No Duty label, no Equip. tag Duty label Duty label + Equip. tag Equip. tag only Special label requirement |
Product version: [v] | E I R Note: |
Zone 2/22, Class I/II Div 2 Zone 0/21, Class I/II Div 1 Zone 0/21, Class I/II Div 1 with EOL and/or series devices Versions E, I & R: IECEx, ATEX, UL, cUL, ULC |
Product option: [o] | 1 W X |
Standard product Alternate EOL & series wiring Custom configuration – contact E2S |
Enclosure colour: [x] | R G S |
Red Grey Special – contact E2S for alternative enclosure colours |
LED indicator: [u]: | N L C Note: |
No LED LED with 1.5K ballast resistor LED without ballast resistor <20mA LED only available with Product version ‘R’ |
For product version E and R only, suffix the part code with required EOL and series devices as follows for factory installation. See the D2xH1-E and D2xH1-IR installation manuals for resistance, wattage and diode specifications: |
||
E.O.L.Module: [e] optional |
ExxxR ED1 ExxxZ |
Resistor value in Ohms e.g. E470R = 470 Ohm Diode IN5401 = ED1 Zener diode e.g. E5V1Z = 5.1V |
Series Module: [s] optional |
SxxxR SD1 SxxxZ |
Resistor value in Ohms e.g. S1K5R = 1.5K Ohm Diode IN5401 = SD1 Zener diode e.g. S5V1Z = 5.1V |
D2xH1-E: Product version: E
IECEx / ATEX
Ex db ec IIC T6 Gc Ta –40°C to +50°C
Ex tc IIIC T55°C Dc Ta –40°C to +50°C
NEC Class Zone
Class I Zone 2 AEx db ec IIC T6 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC T55°C Dc Ta -40°C to +50°C
CEC Class Zone
Ex db ec IIC T6 Gc Ta –40°C to +50°C
Ex tc IIIC T55° Dc Ta –40°C to +50°C
NEC / CEC Class Division
Class I Div 2 ABCD T6 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 2 Ta -40°C to +50°C
D2xH1-I: Product version: I
IECEx / ATEX
Ex ia IIC T6 Ga Ta –40°C to +50°C
Ex tb IIIC T75°C Db Ta –40°C to +50°C
NEC Class Zone
Class I Zone 0 AEx ia IIC T6 Ga Ta -40°C to +50°C
Zone 21 AEx tb IIIC T75°C Db Ta -40°C to +50°C
CEC Class Zone
Ex ia IIC T6 Ga X Ta -40°C to +50°C
Ex tb IIIC T75°C Db X Ta -40°C to +50°C
NEC / CEC Class Division
Class I Div 1 Group ABCD T6 Ta -40°C to +50°C
Class II Div 2 Group FG T6 Ta -40°C to +50°C
Class III Div 2 Ta -40°C to +50°C
D2xH1-IR: Product version: R
IECEx / ATEX
Ex ia IIC T4 Ga Ta –40°C to +50°C
Ex tb IIIC T75°C Db Ta –40°C to +50°C
NEC Class Zone
Class I Zone 0 AEx ia IIC T4 Ga Ta -40°C to +50°C
Zone 21 AEx tb IIIC T75°C Db Ta Ta -40°C to +50°C
CEC Class Zone
Ex ia IIC T4 Ga X Ta -40°C to +50°C
Ex tb IIIC T75°C Db X Ta -40°C to +50°C
NEC / CEC Class Division
Class I Div 1 Group ABCD T4 Ta -40°C to +50°C
Class II Div 2 Group FG T4 Ta -40°C to +50°C
Class III Div 2 Ta -40°C to +50°C
See installation manuals for full coding